EST-BK901 Conventional Reflective Beam Detector has built in Laser beam pointing and Digital guide display for real user friendly alignment method. The Laser beam pointing accurately point the exact location where to mount mirror and with additional digital guide display allows to monitor and guide on the actual light intensity between the mirror and detector which cannot be seen by our naked eye making it more easy and convenient in alignment commissioning. The AW-BK901 has four adjustable operational ranges of between 8 to 20, 20 to 40, 40 to 70 and70to100meters beside with three adjustable sensitivity setting ranges from 2.6dB, 3.8dB and 5.8dBtomeetthespecific environmental requirement. The EST-BK901 works on the principle of reflective infrared beam obscuration. Used in conjunction with a reflector, it will notify the fire alarm panel when the infrared beam is obscured by smoke.
Part Number | EST-BK901 |
---|---|
Listed | LPCB / CE-CPR |
Compliance | EN54-12:2002 |
Power | BS 5839 Part 1:2002 |
Operating Voltage | 20 V to 28 V DC |
Current Parameters | Standby:23mA Commission:56mA Alarm:33mA |
Beam Sensor Sensitivity [via Encoder] | Level 1: 2.6 dB High Sensitivity |
Beam Pathway Length [via Encoder] | Span 1: 8 to 20 meters Short Path (1x mirror reflector required) |
Beam Path Angle | ±0.5º Directional |
Alignment Guide | Laser Beam Pointer |
LED Indicator Guide | Nixie Tube |
Reset Time | Less than 2 Second (Power Cut) |
Relay Capacity [Fire & Fault] | Normally Open/ 2.0 A; 30 VDC |
Material / Colour | ABS / White |
Dimension / Weight | L:190.87 x W:126.87 x H:91.96 mm / 440 gm |
Weight | 0.130 Kg with base |
Accessories | Mounting Bracket/ AW-BK901-R 4 x Mirror Reflector |
Operating Temperature / Protection Rating | -10°C to 55°C / IP30 [IP66 glue seal-For permanent fixing] |
Humidity | 0 to 95% Relative Humidity, Non condensing |
Copyright © 2023 Eurologic Science & Technology (EST) . All Rights Reserved.